REBY 75267 UPC#650737449261
Item #: 44926
The SER series lowers demand on air conditioning systems. Air supplied from outdoors enters through the energy recovery core where it transfers the heat and moisture from the incoming air to the outgoing air that was cooled and dried by the building's air conditioner. The air brought into the working area is cooled and the humidity is reduced for maximum comfort. Reduces the load on an air conditioner to save on cooling costs. This unit is designed for warmer, humid climates with longer cooling seasons.
Applications include classrooms, retails shops, hair salons, bars and restaurants, offices, clinics, and animal shelters, etc.
Unit | ||
---|---|---|
Frequency | 60 | Hz |
Voltage (nominal) | 120 | V |
Phases | 1~ | |
Input current | 11 | A |
Air flow | 786 | cfm |
Nominal max static pressure (in. w.g.) | 0.4 | in.wg |
Heat Exchanger | ||
---|---|---|
Heat exchanger | Energy recovery |
Others | ||
---|---|---|
Installation type | False ceiling; Horizontal |
Dimensions and weights | ||
---|---|---|
Weight | 209.9 | lb |
|
Supply temperature | Net airflow | Sensible recovery efficiency | Latent recovery efficiency | Total recovery efficiency |
°F (°C) |
cfm (L/s) |
% |
% |
% |
|
Heating |
35 (1.7) |
560 (264) |
67 |
39 |
57 |
35 (1.7) |
420 (198) |
70 |
46 |
62 |
|
Cooling |
95 (35) |
560 (264) |
64 |
28 |
42 |
95 (35) |
420 (198) |
67 |
34 |
47 |
A | B | C | D | E | F | G | I | J | K Drain Spout |
51 2/5 (1306) |
47 1/5 (1199) |
20 (508) |
3 (76) |
8 (203) |
8 (203) |
36 1/4 (921) |
22 (559) |
32 1/2 (826) |
1/2 (13) |