FIT 70E Fresh Air Appliance

Ceiling ERV, 70 cfm

Item #: 463400

The lightweight FIT 70E features a slim profile, side port connection, energy recovery core, supply fan modulation for frost prevention, and more. This 70 cfm appliance is ideally suited for condominiums and apartments.

 

• Side port 4” duct connection

• Up to 70 cfm @ 0.4 in.wg.

• Multi-speed operation to fit airflow needs

• Frost prevention for year-round functionality

• External electrical box for quick & easy access

• Lightweight design allows for easy installation in tight spaces

• No drain required resulting in less maintenance

• Easy ceiling or wall installation

 

The FIT 70E profiles at a size of only 18.5” x 19.5” and 9.75”, and is lightweight & compact. The AHRI certified core made from water vapor transport durable polymer membrane is highly permeable to humidity. In addition, the ERV core is freeze tolerant and water washable. The core, filters, fans, and electrical panel can be accessed easily from the access panel.

 

The FIT 70E brings a continuous supply of fresh air into the premises while exhausting an equal amount of contaminated air out. The energy recovery core transfers both heat and moisture from the outgoing exhaust air to the incoming fresh air reducing the energy required to condition it. In summer time, the appliance cools and removes humidity from the fresh air and in winter time, it heats it while retaining humidity to keep the living area comfortable year-round.

 

This fresh air appliance is equipped with a preset frost prevention sequence that is activated at an outdoor air temperature of 14°F (-10°C) and lower. During the sequence, the supply blower shuts down and the exhaust blower switches into high speed to maximize the effectiveness of the frost prevention method. The appliance then returns to normal operation to continue the cycle.

 

The Fit 70E comes with two washable MERV3 electrostatic filters, a removable screw terminal for easy connection with external access, and metal collars with rubber gaskets to ensure a tight connection on the rigid duct. The appliance comes with a limited warranty: 5 years on energy recovery core, 7 years on motors, and 5 years on electrical parts.

 

The appliance has been tested in accordance with Home Ventilating Institute (HVI) Certification Program to ensure it meets HVI ratings for airflow and energy.

Technical parameters

Product
Voltage (nominal) 120 V
Input power 58 W
Input current 1.1 A
Air flow 70 cfm
Nominal max static pressure (in. w.g.) 0.4 in.wg
Certificate CSA, HVI
Air flow, max [m³/h] 75 cfm or less cfm
Exchanger
Heat exchanger Energy recovery
Dimensions and weights
Weight 31.7 lb
Used for
Installation type Ceiling
 

Supply temperature​

Net airflow

Consumed power

Sensible recovery efficiency

Adjusted sensible recovery efficiency

Latent recovery / moisture transfer

 

°F(°C)

cfm (L/s)

W

%

%

%

Heating

32 (0)

51 (24)

40

70

75

45

 

32 (0)

59 (28)

44

67

72

42

 

32 (0)

70 (33)

52

65

69

40

 

5 (-15)

55 (26)

42

55

58

35

 

-13 (-25)

59 (28)

34

34

35

21

 

Supply temperature​

Net airflow

Consumed power

Total recovery efficiency

Adjusted total recovery efficiency

Latent recovery / moisture transfer

Cooling

°F(°C)

cfm (L/s)

W

%

%

%

95 (35)

51 (24)

40

40

43

30

RFA
DXF

GUIDE SPECIFICATION

Specifier Notes: This guide specification is written in Construction Specifications Institute (CSI) 3-Part Format in accordance with The CSI Construction Specifications Practice Guide, MasterFormat, SectionFormat, and PageFormat.

Specifier Notes: This Section must be carefully reviewed and edited by the Architect or Engineer to meet the requirements of the Project and local building code. Coordinate this Section with Division 01, other specification sections, and the Drawings. Delete all Specifier Notes after editing this Section.

Section numbers and titles are based on MasterFormat 2016 Update.

 

SECTION 23 72 00

AIR-TO-AIR ENERGY RECOVERY VENTILATOR

Specifier Notes: This Section covers Fantech’s FIT 70E Energy Recovery Ventilators. Consult Fantech for assistance in editing this Section as required for the Project.

 

PART 1. GENERAL

1.1 SECTION INCLUDES

    A. Energy Recovery Ventilators

 

1.2 RELATED REQUIREMENTS

Specifier Notes: Edit the following list of related sections as required for the Project. Limit the list to sections with specific information that the reader might expect to find in this Section but is specified elsewhere.

    A. Section 23 08 00 – Commissioning of HVAC

 

1.3 REFERENCE STANDARDS

Specifier Notes: List reference standards used elsewhere in this Section, complete with designations and titles. Delete reference standards from the following list not used in the edited Section.

    A. ASHRAE 84 – Standard for Testing Air-to-Air Heat/Energy Exchangers

    B. AHRI 1060 – Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation Equipment

    C. CSA C22.2 No. 77/UL2111 Standard for Safety Overheating Protection for Motors

    D. CSA C22.2, No. 113 – Fans and Ventilators

    E. CSA C439 – Laboratory Methods of Test for Rating the Performance of Heat/Energy-Recovery Ventilators

    F. CSA F326 – Residential Mechanical Ventilation Systems

    G. IEC 60529, Class 44 – Ingress Protection Test Standard

    H. ISO 846a and ISO846c – Antimicrobial Test – Plastics

    I. ISO 9001:2015 – Quality Management Systems – Requirements

    J. NFPA 70 – National Electrical Code (NEC)

    K. UL723 – Standard for Test for Surface Burning Characteristics of Building Materials

    L. UL900 – Standard for Safety Air Filter Units

    M. UL1004 – Standard for Safety Electric Motors

    N. UL1812 – Standard for Ducted Heat Recovery Ventilators

 

1.4 PREINSTALLATION MEETINGS

Specifier Notes: Edit the Preinstallation Meetings article as required for the Project. Delete article if not required.

    A. Convene preinstallation meeting [1 week] [2 weeks] before start of Work of this Section.

    B. Require attendance of parties directly affecting Work of this Section, including Contractor, Architect, installer, and manufacturer’s representative.

    C. Review the Following:

        a. Materials

        b. Installation

        c. Adjusting

        d. Protection

        e. Coordination with other Work

 

1.5 SUBMITTALS

Specifier Notes: Edit the Submittals article as required for the Project. Delete submittals not required.

    A. Comply with Division 01.

    B. Product Data: Submit manufacturer’s product data, including installation instructions.

    C. Shop Drawings: Submit manufacturer’s shop drawings, including plans, elevations, sections, and details.

        a. Wiring Diagrams: Indicate wiring for each item of equipment and interconnections between items of equipment.

        b. Include manufacturer’s names, model numbers, ratings, power requirements, equipment layout, device arrangement, complete wiring point-to-point diagrams, and conduit layouts.

    D. Manufacturer’s Certification: Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application.

    E. Operation and Maintenance Data:

        a. Submit manufacturer’s operation and maintenance manual; including the following:

            i. Operation, maintenance, adjustment, and cleaning instructions,

             ii. Troubleshooting guide,

            iii. Parts list, and

            iv. Electrical wiring diagrams if required.

        b. Provide detailed information required for Owner to properly operate and maintain equipment.

    F. Warranty Documentation: Submit manufacturer’s standard warranty.

1.6 QUALITY ASSURANCE

    A. Manufacturer’s Qualifications:

        a.    Manufacturer regularly engaged in the manufacturing of air handling units, heat, or energy recovery ventilators in the last 10 years.

        b. ISO 9001 Certified

    B. Installer's Qualifications:

        a. Installer regularly engaged in installation of air handling units, heat, or energy recovery ventilators to that specified for a minimum of 5 years.

        b. Use persons trained for installation of air handling units, hear or energy recovery ventilators.

 

1.7 DELIVERY, STORAGE, AND HANDLING

    A. Delivery Requirements: Deliver materials to site in manufacturer’s original, unopened containers, and packaging, with labels clearly identifying product name and manufacturer.

    B. Storage and Handling Requirements:

        a. Store and handle materials in accordance with manufacturer’s instructions,

        b. Keep materials in manufacturer’s original, unopened containers, and packaging until installation,

        c. Store materials in clean, dry area indoors,

        d. Keep materials from freezing, and

        e. Protect materials during storage, handling, and installation to prevent damage.

 

1.8 WARRANTY

Warranty Period: 5 years on energy recovery core, 7 years on motors, and 5 years on parts.

 

PART 2. PRODUCTS

2.1 MANUFACTURERS

    A. Manufacturer: Fantech Inc., 50 Kanalflakt Way, Bouctouche, New Brunswick E4S 3M5, Canada. For Canada: Toll Free 800-565-3548, CANADAsupport@fantech.net

For USA: Toll Free 800-747-1762, USsupport@fantech.net

Specifier Notes: Specify if substitutions will be permitted.

    B. Substitutions: [Not permitted] [Comply with Division 01].

    C. Single Source: Provide materials from single manufacturer.

 

2.2 ENERGY RECOVERY VENTILATORS

    A. Energy Recovery Ventilators: FIT 70E

        a. Model: FIT 70E

        b. Indoor, compact, residential energy recovery ventilators

Specifier Notes: Specify required model. Consult Fantech for assistance in determining energy recovery ventilator model for the specific application.

    B. General

        a. Each Unit or Group of Units: Capable of operating in any mode independently or dependently of other systems.

        b. Listed under CSA C22.2, No. 113/UL 1812

        c. Wiring: NFPA 70

        d. Performance: As scheduled on the Drawings

        e. Equipped with a control system.

        f. Performs all functions necessary for operation.

        g. Ventilation to Building: Not to cease in any mode based solely on operational temperature of minus 13 to 104 degrees F (minus 25 to 40 degrees C).

        h. Capable of changing modes with no interruption to system operation.

        i. Capable of transferring both sensible and latent heat between the fresh and stale air streams.

        j. Capable of operating in winter and summer conditions without imbalance or loss of ventilation capacity greater than specified in design.

    C. Unit Cabinet

        a.    Single Wall Cabinet:

            i. 22-gauge G90 galvanized corrosion resistant steel case (pre-painted door)

            ii. Seams: Sealed, requiring no caulking in field

        b. Insulation within a Single Wall:

            i. 1.0-inch (25-mm) of high-density polystyrene

            ii. Flame Spread Index, UL 723: Not over 25

            iii. Smoke Developed Index, UL 723: Not over 50

    D. Cabinet Doors & Panels

        a. Pre-painted door

        b. 1.0-inch (25-mm) high-density polystyrene covered with 0.25-inch (6.4-mm) closed cell flexible elastomeric foam insulation

    E. Fans

        a. Factory-balanced fans with backward curved blades

        b. Fan Motors:

            i. Maintenance-free, permanently lubricated, sealed ball bearings

            ii. Thermal overload protected (TOP)

            iii. UL listed to UL1004 and/or UL2111, CSA C22.2 No. 77 and No.100

            iv. IP Protection: Class 44 according to IEC 60529

        c. Separate fans for exhaust and supply blowers.

    F. Energy recovery core

        a. Exchanger Construction: Flame rated polymer membrane designed to transfer sensible and latent energy. The flame spread index of the energy recovery exchanger shall not be over 25 and its smoke developed index shall not be over 50 when tested in accordance with the Standard for Tests for Surface Burning Characteristics of Building Material, UL723. Mold and Bacteria resistance tested to ISO 846a and ISO 846c with a rating of 0 for both. The ERV Core is freeze tolerant and water washable.

        b. Cross-flow construction type

        c. Performance: Certified and listed by AHRI.

        d. Frame Material: Corner profiles in PVC and gables in aluminum-zinc sheet steel.

        e. Effectiveness of exchanger: Documented in accordance with ASHRAE 84 and AHRI 1060.

        f. Flame Spread Index, Energy Recovery Exchanger, UL 723: Not over 25

        g. Smoke Developed Index, Energy Recovery Exchanger, UL 723: Not over 50

    G. Air filters

        a. Supply and exhaust air protected by 2 washable electrostatic panel type air filters.

        b. 8.5" (216mm) x 8" (205mm) x 0.125" (3mm) that meet UL 900 (Optional MERV8 or MERV13 filters are direct replacement to the MERV3 in size).

    H. Frost prevention

        a. Frost prevention sequence (pre-set) initiated if the outdoor air temperature falls below the set point of 14°F (-10°C).

    I. Electrical 1 Phase Input Voltage

        a. Electrical Power: 120 VAC, 1 Phase, 60 Hz, MOP 15A

        b. Internal Electrical Components:

            i. Factory wired for single-point power connection.

            ii. UL Listed or Recognized and CSA Certified or Accepted where applicable and wired in compliance with the National Electrical Code.

    J. Electrical Box Components: Accessible without stopping unit or opening doors.

    K. Electrical Box:

        a. Isolated from airflow paths.

        b. Protects integral wires and connections.

    L. Serviceability

        a. Access Panel: hinged and/or screwed access panel on front of unit.

        b. Energy Recovery Exchangers, Filters, and Motors: serviceable from front of unit.

        c. Fan Assemblies: mounted on removable sliding base.

        d. Energy Recovery Exchangers and Filters: mounted on slide-out rails.

 

2.3 ACCESSORIES

    A. Volatile Organic Compound (VOC) Sensing Control: ECO-Feel Auto IAQ.

 

2.4 ASSEMBLY

    A. Factory assembled and wired energy recovery ventilators.

 

2.5 SOURCE QUALITY CONTROL

    A. Run test at factory.

 

PART 3. EXECUTION

3.1 EXAMINATION

    A. Examine areas to receive energy recovery ventilators.

    B. Notify Architect of conditions that would adversely affect installation or subsequent use.

    C. Do not begin installation until unacceptable conditions are corrected.

 

3.2 PREPARATION

    A. Prepare surfaces where energy recovery ventilators are to be mounted.

    B. Ensure surfaces are flat, level, plumb, and can support weight of energy recovery ventilators.

 

3.3 INSTALLATION

    A. Install energy recovery ventilators in accordance with manufacturer’s instructions at locations indicated on the Drawings.

    B. Unit is typically hung by using metal mounting bracket supplied with unit.

    C. Optional chain kit available

    D. Install energy recovery ventilators in accordance with NFPA 70.

    E. Do not expose electronic components to temperatures below 32 degrees F (0 degrees C) or above 122 degrees F (50 degrees C).

 

3.4 ADJUSTING

    A. Adjust energy recovery ventilators for proper operation in accordance with manufacturer’s instructions.

 

3.5 DEMONSTRATION

    A. Demonstration

        a. Demonstrate that energy recovery ventilators function properly in every respect.

        b. Provide hands-on demonstrations of operation of system components and complete system, including user-level program changes and function.

        c. Provide instruction and training by factory-trained and certified representative of manufacturer.

 

3.6 PROTECTION

    A. Protect installed energy recovery ventilators from damage during construction.

 

END OF SECTION

ECO-Feel® Auto IAQ control - Fantech
Item #: 414729
ECO-Feel® Auto IAQ control

TVOC sensing controller, ECO-mode, w/o display, 4 wires

.
COM4P Supply and Exhaust Hoods - Fantech
Item #: 40369
COM4P Supply and Exhaust Hoods

4" White Plastic Supply & Exhaust Hoods (pair)

.
FIDT 4 Insulated Flex Duct - Fantech
Item #: 411061
FIDT 4 Insulated Flex Duct

4" flexible duct, R4.2 Rating, 25ft

.
MATRIX 6, 2 in 1 Vent Hood - Fantech
Item #: 413640
MATRIX 6", 2 in 1 Vent Hood

tandem, supply/exhaust hood, 6” duct

.
Filter,MERV3,70 cfm,Repl.kit - Fantech
Item #: 405116
Filter,MERV3,70 cfm,Repl.kit

Washable Alu mesh MERV3 filter kit, 70 cfm, 2 pcs, 8"x8.3"

.
Filter,MERV6,70 cfm,Repl.kit - Fantech
Item #: 414644
Filter,MERV6,70 cfm,Repl.kit

MERV6 Filter kit, 70 cfm, 2 pcs, 8"x8.5"

.
MGE 4 Metal Exhaust Grill - Fantech
Item #: 411106
MGE 4 Metal Exhaust Grill

4" duct metal grille w/collar, exhaust

.
MGS 4 Metal Supply Grill - Fantech
Item #: 411368
MGS 4 Metal Supply Grill

4" duct metal grille w/collar, supply

.