Ceiling ERV w/shut-off damper, 127 cfm
Item #: 463403
With an integrated mechanical shutoff damper, the FIT 120E-D fresh air appliance gives you options to meet your desired installation scheme.
• Airflow up to 129 cfm @ 0.4” wg.
What sets this appliance apart from the rest of the FIT series is the integrated mechanical shutoff damper. This damper prevents outside air from being pulled back into the space through the supply ductwork when the unit is in standby or defrost mode. Constructed of polymeric material, the damper is activated by a non fail-safe actuator.
This fresh air appliance, designed for multi-family residential applications, brings a continuous supply of fresh air into the premises while exhausting an equal amount of contaminated air out. As such, the energy recovery core transfers both heat and moisture from the outgoing exhaust air to the incoming fresh air, reducing the energy required to condition it.
The FIT 120E-D houses an energy recovery core that is constructed from water vapor transport durable polymer membrane and is highly permeable to humidity. In addition, the ERV core is freeze tolerant and water washable. The core, filters, fans, and electrical panel can be accessed easily from the access panel.
Multi-speed operation fits an abundance of airflow needs. The external electrical box allows for quick & easy access. Mount these appliances within a ceiling or wall, made to “fit” within bulkheads or over false ceilings. Thanks to the no drain application, less maintenance is required as well.
The appliance is equipped with a preset frost prevention sequence that is activated at an outdoor air temperature of 14°F (-10°C) and lower. During the sequence, the supply blower shuts down, the mechanical shutoff damper closes & the exhaust blower switches into high speed to maximize the effectiveness of the frost prevention strategy. The appliance then returns to normal operation and continues the cycle.
The FIT 120E-D comes with two washable electrostatic panel type air filters and metal collars with rubber gaskets to ensure a tight connection on rigid ductwork.
Limited warranty: 5 years on energy recovery core, 7 years on motors, and 5 years on electrical parts.
This appliance has been tested in accordance with CSA C439 and is certified by the Home Ventilation Institute (HVI) to ensure the validity of its published performance ratings.
Product | ||
---|---|---|
Voltage (nominal) | 120 | V |
Phases | 1~ | |
Input power | 120 | W |
Input current | 1 | A |
Air flow | 127 | cfm |
Certificate | CSA, HVI | |
Air flow, max [m³/h] | 76-130 cfm | cfm |
Exchanger | ||
---|---|---|
Heat exchanger | Energy recovery |
Dimensions and weights | ||
---|---|---|
Weight | 32.6 | lb |
Used for | ||
---|---|---|
Installation type | Ceiling; False ceiling |
Supply temperature |
Net airflow |
Consumed power |
Sensible recovery efficiency |
Adjusted sensible recovery efficiency |
Latent recovery/ moisture transfer |
|
°F(°C) |
cfm (L/s) |
W |
% |
% |
% |
|
Heating |
32 (0) |
51 (24) |
55 |
74 |
81 |
76 |
32 (0) |
68 (32) |
63 |
69 |
75 |
71 |
|
32 (0) |
131 (62) |
104 |
64 |
69 |
60 |
|
-13 (-25) |
51 (24) |
55 |
61 |
63 |
54 |
|
Supply temperature |
Net airflow |
Consumed power |
Total recovery efficiency |
Adjusted total recovery efficiency |
Latent recovery / moisture transfer |
|
°F(°C) |
cfm (L/s) |
W |
% |
% |
% |
|
Cooling |
95 (35) |
51 (24) |
55 |
64 |
68 |
68 |
A |
B |
C |
D |
E |
F |
Duct size |
23 5/32 (588) |
20 3/4 (527) |
25 1/16 (636) |
20 27/32 (529) |
10 (254) |
9 1/4 (235) |
5 (125) |
Dimensions in inches (mm). |