SHR 800 Heat Rec Ventilator

Item Number: 99270

• Airflow up to 794 cfm @ 0.4" PS
• Push-push configuratio
• Removable screw terminal for easy connection
• Dual service doors & reversible electrical box
• External three position switch (Low/Standby/High)

Application

The SHR 800 Commercial Heat Recovery Ventilation system (HRV) complements today's tight buildings.

How it works

Fantech Heat Recovery Ventilators (HRV) are designed to supply air into a building while exhausting an equal amount of contaminated air to the outside. The aluminum heat exchanger core transfers sensible energy between air streams resulting in tempering of the supply air and reduced loads on the HVAC system.

Defrost cycle

A preset defrost sequence is activated at an outdoor air temperature of 23°F and lower. During the defrost sequence, the supply blower shuts down & the exhaust blower switches to high speed to maximize the effectiveness of the defrost strategy. The unit then returns to normal operation, and continues the cycle.

Technical parameters

Unit
Frequency 60 Hz
Voltage (nominal) 120 V
Phase(s) 1~
Input current 5.3 A
MCA 7.13 A
MOP 15 A
Input power 636 W
Air flow max 795.0 cfm
Static pressure 0.4 in.wg
Dimensions and weights
Weight 157.6 lb
Certificates
Certificate CSA, AHRI
Supply Temperature Net Airflow Net Effectiveness

Sensible

Total

°F (°C)

cfm (L/s)

%

%

Heating

35 (1.7)

690 (326)

57

37

35 (1.7)

518 (244)

61

40

Cooling

95 (35)

690 (326)

47

18

95 (35)

518 (244)

49

19

A B C D E F G

36 1/2 (927)

32 3/16 (818)

20 (508)

8 (203)

21 1/2 (546)

35 (889)

25 3/4 (654)

Fans

Two (2) factory balanced fans with backward curved blades. Motors come with permanently lubricated sealed ball bearings, (TOP) thermal overload protected and maintenance-free operation.

Heat recovery core

Fantech manufactures this fixed plate cross-flow heat exchanger using new 1100 alloy aluminum. Heat exchanger is engineered with a turbulence inducing geometry in order to maximize heat transfer while allowing an effective evacuation of condensate. The plates are hemmed and sealed to ensure no cross-contamination of airstreams. The aluminum core had a plastic handle for easy removal. The SHR 800 features two cores, each 12" x 12" (305 mm x 305 mm) with a 15" (380 mm) depth.

Defrost

A preset frost control sequence is initiated if the outdoor temperature falls below the set point of 23°F (-5°C). During the initial stage, the supply blower shuts down & the exhaust blower switches into high speed to eliminate frost build-up in the core. The unit then returns to normal operation for the final stage of the frost control sequence at which time the sequence is repeated if the outdoor air temperatures is still below the set point.

Serviceability

Cores, filters and drain pan can be accessed easily from both sides of the HRV from hinged access panels. Cores conveniently slide out with only 15" (380 mm) clearance. Blowers can be accessed from both side of the HRV from fastened access panels. Blowers are easily removed by taking off the access panel and sliding the motor plates out of the HRV. A quick connect allows for fast inspection of blowers.

Case

22 gauge galvanized steel. Baked powder coated paint.

Insulation

Insulated with 1 in. (25 mm) fiberglass with FSK facing and 2 in. (50 mm)of foil-faced high density polystyrene foam on the outdoor air side for condensation control.

Filters

The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL 900. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 0.76 in.wg (190 Pa) at 800 cfm (378 l/s). Additional MERV Rated filters available upon request.

Controls

External three (3) position (Low/Stand By/High) rocker switch that will offer continuous ventilation. In addition Fantech offers a variety of external controls.

Mounting

Unit may be suspended by using threaded rod, not supplied, or placed on a platform. Unit shall be adaptable for easy service of electrical component.

Warranty

Limited lifetime on aluminum core, 3 years on motors, and 3 years on parts

Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Technical data was obtained from published results of test relating to AHRI 1060 Standards
BPM 08-20 Bypass module Item Number: 99301 BPM 08-20 Bypass module .
CO2RT-R Transmitter Item Number: 99315 CO2RT-R Transmitter .
ECO-TOUCH® Pgrm Wall Control Item Number: 44929 ECO-TOUCH® Pgrm Wall Control .
EDF1 Multi-Func Ctrl Item Number: 40375 EDF1 Multi-Func Ctrl .
EDF7 Elec Multi-Funct Dehum Item Number: 44883 EDF7 Elec Multi-Funct Dehum .
EFD 20-8, Damper, TFB24 Item Number: 99304 EFD 20-8, Damper, TFB24 .
IR 4 Iris Damper Item Number: 411234 IR 4 Iris Damper .
IR 5 Iris Damper Item Number: 411235 IR 5 Iris Damper .
IR 6 Iris Damper Item Number: 411236 IR 6 Iris Damper .
IR 8 Iris Damper Item Number: 411237 IR 8 Iris Damper .
MDEH1 Low Voltage Dehumidistat Item Number: 40172 MDEH1 Low Voltage Dehumidistat .
MGE 4 Metal Exhaust Grill Item Number: 411106 MGE 4 Metal Exhaust Grill .
MGE 5 Metal Exhaust Grill Item Number: 411370 MGE 5 Metal Exhaust Grill .
MGE 6 Metal Exhaust Grill Item Number: 411371 MGE 6 Metal Exhaust Grill .
MGE 8 Metal Exhaust Grill Item Number: 411244 MGE 8 Metal Exhaust Grill .
MGS 4 Metal Supply Grill Item Number: 411368 MGS 4 Metal Supply Grill .
MGS 5 Metal Supply Grill Item Number: 411369 MGS 5 Metal Supply Grill .
MGS 6 Metal Supply Grill Item Number: 411242 MGS 6 Metal Supply Grill .
MGS 8 Metal Supply Grill Item Number: 411243 MGS 8 Metal Supply Grill .
RTS2 Pushbutton Timer Item Number: 40164 RTS2 Pushbutton Timer .
RTS5 Pushbutton Timer Item Number: 44794 RTS5 Pushbutton Timer .