ECOM Symbol ECOM Symbol

SER 1100 Energy Rec Vent

Side duct connection ERV, 1179 cfm

Item Number: 99277

 

• Airflow up to 1179 cfm @ 0.4" PS
• Push-Pull configuration
• Optional drain line
• Removable screw terminal for easy connection
• Dual service doors & reversable electrical box
• External three position switch (Low/Standby/High)
Application

Fantech® commercial energy recovery ventilators (ERV) models provide cost-effective energy savings while delivering ventilation to buildings in a compact product.

Applications include classrooms, retails shops, hair salons, bars and restaurants, offices, clinic, and animal sheters, etc.

How it works

The exchanger tempers the outdoor air before supplying it to the building by recovering the energy in the building’s air before exhausting it. In summer, the ERV will pre-cool and reduce moisture in the ventilation air while in winter it will pre-heat and recover moisture. We designed our commercial energy recovery ventilators to operate in both warm and humid climates and in very cold climates.

Technical parameters

Unit
Frequency 60 Hz
Voltage (nominal) 120 V
Phase(s) 1~
Input current 11.17 A
MCA 13.75 A
MOP 15 A
Input power 1,340 W
Air flow max 1,178 cfm
Static pressure 0.4 in.wg
Dimensions and weights
Weight 209.9 lb
Certificates
Certificate CSA, AHRI
Images Wiring - SER 1100 Energy Rec Vent - Fantech
Supply Temperature Net Airflow Net Effectiveness

Sensible

Latent

Total

°F (°C)

cfm (L/s)

%

%

%

Heating

35 (1.7)

840 (396)

54

35

50

35 (1.7)

630 (297)

57

40

54

Cooling

95 (35)

840 (396)

51

32

49

95 (35)

360 (297)

60

37

53

Images Dimensions - SER 1100 Energy Rec Vent - Fantech
A B C D E F G I J K Drain Spout

51 2/5 (1306)

47 1/5 (1199)

20 (508)

3 (76)

8 (203)

8 (203)

36 1/4 (921)

22 (559)

32 1/2 (826)

1/2 (13)

Dimensional information is in inches (mm)

Fans

Four (4) factory balanced fans with backward curved blades. Motors come with permanently lubricated sealed ball bearings and (TOP) thermal overload protected and maintenance-free operation.

Energy recovery core

Three (3) modular AHRI certified energy recovery cores made from water vapor transport durable polymer membrane that is highly permeable to humidity. The ERV core is freeze tolerant and water washable. Core dimensions are 11.5" x 11.5" (290x 290 mm) with a 15" (380 mm) depth.

Defrost

A preset frost control sequence is initiated if the outdoor temperature falls below the set point of 23°F (-5°C). During the initial stage, the supply blower shuts down & the exhaust blower switches into high speed to eliminate frost build-up in the core. The unit then returns to normal operation for the final stage of the frost control sequence at which time the sequence is repeated if the outdoor air temperatures is still below the set point.

Serviceability

Cores, filters and drain pan can be accessed easily from both sides of the ERV from hinged access panels. Cores conveniently slide out with only 15" (380 mm) clearance. Blowers can be accessed from both side of the ERV from fastened access panels. Blowers are easily removed by taking off the access panel and sliding the motor plates out of the ERV. A quick connect allows for fast inspection of blowers.

Case

22 gauge galvanized steel. Baked powder coated paint.

Insulation

Insulated with 1in. (25 mm) fiberglass with FSK facing for condensation control.

Filters

The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL 900. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 0.64 in.wg (160 Pa) at 1100 cfm (519 l/s). Additional MERV Rated filters available upon request.

Drain

A Drain and Tubing (included) must be installed for all HRV units. For ERV units, drain is not required,however, it is recommended for climates where outdoor temperature typically remains below -25°C(-13°F) combined with an indoor relative humidity higher than 40% for a period of 24 hours or severaldays in a row.

Controls

External three (3) position (Low/Stand By/High) rocker switch that will offer continuous ventilation. In addition Fantech offers a variety of external controls.

Mounting

Unit may be suspended by using threaded rod, not supplied, or placed on a platform. Unit shall be adaptable for easy service of electrical component.

Warranty

3 years on all parts

Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Technical data was obtained from published results of test relating to AHRI 1060 Standards
CO2RT-R Transmitter - Fantech Item Number: 99315 CO2RT-R Transmitter

0-2000ppm w/relay, room mounting

.
ECO-Feel - Fantech Item Number: 414729 ECO-Feel

Dehumidistat & IAQ sensor, w/o display, 4 wire

.
ECO-Touch® IAQ - Fantech Item Number: 414727 ECO-Touch® IAQ

Touchscreen multi-function dehumidistat, 4 wires

.
EDF1 Multi-Func Ctrl - Fantech Item Number: 40375 EDF1 Multi-Func Ctrl

Low-Intermittent-High Wall Control

.
EDF7 Electronic Dehumidistat - Fantech Item Number: 44883 EDF7 Electronic Dehumidistat

multi-function, surface mount

.
EFD 20-8, Damper, TFB24 - Fantech Item Number: 99304 EFD 20-8, Damper, TFB24

20"x8" Shutter damper with spring-return actuators, 24V

.
Filter,MERV8,1100-1400,Repl.ki - Fantech Item Number: 414934 Filter,MERV8,1100-1400,Repl.ki

MERV8 Filter kit, LC, 1100-1400cfm, 6 pcs, 11.5"x15"

.
IR 4 Iris Damper - Fantech Item Number: 411234 IR 4 Iris Damper

4" iris damper w/manual adjuster

.
IR 5 Iris Damper - Fantech Item Number: 411235 IR 5 Iris Damper

5" iris damper w/manual adjuster

.
IR 6 Iris Damper - Fantech Item Number: 411236 IR 6 Iris Damper

6" iris damper w/manual adjuster

.
IR 8 Iris Damper - Fantech Item Number: 411237 IR 8 Iris Damper

8" iris damper w/manual adjuster

.
MDEH1 Low Voltage Dehumidistat - Fantech Item Number: 40172 MDEH1 Low Voltage Dehumidistat

2-wire mechanical dehumidistat, low voltage

.
MGE 4 Metal Exhaust Grill - Fantech Item Number: 411106 MGE 4 Metal Exhaust Grill

4" duct metal grille w/collar, exhaust

.
MGE 5 Metal Exhaust Grill - Fantech Item Number: 411370 MGE 5 Metal Exhaust Grill

5" duct metal grille w/collar, exhaust

.
MGE 6 Metal Exhaust Grill - Fantech Item Number: 411371 MGE 6 Metal Exhaust Grill

6" duct metal grille w/collar, exhaust

.
MGE 8 Metal Exhaust Grill - Fantech Item Number: 411244 MGE 8 Metal Exhaust Grill

8" duct metal grille w/collar, exhaust

.
MGS 5 Metal Supply Grill - Fantech Item Number: 411369 MGS 5 Metal Supply Grill

5" duct metal grille w/collar, supply

.
MGS 6 Metal Supply Grill - Fantech Item Number: 411242 MGS 6 Metal Supply Grill

6" duct metal grille w/collar, supply

.
MGS 8 Metal Supply Grill - Fantech Item Number: 411243 MGS 8 Metal Supply Grill

8" duct metal grille w/collar, supply

.
Replacement filter kit, MERV13 - Fantech Item Number: 414937 Replacement filter kit, MERV13

Replacement filter kit, MERV13, (1100-1400 cfm)

.
RTS2 Pushbutton Timer - Fantech Item Number: 40164 RTS2 Pushbutton Timer

20 minutes push-button timer

.
RTS5 Pushbutton Timer - Fantech Item Number: 44794 RTS5 Pushbutton Timer

Pushbutton Timer, 20/40/60 minutes

.