for 12" circular ducts, 2" insulation, rubber gaskets
Item #: 411287
Dimensions and weights | ||
---|---|---|
Weight | 31.2 | lb |
Noise suppression dB (mid-frequency Hz) | ||||||||
63 Hz |
125 Hz |
250 Hz |
500 Hz |
1k Hz |
2k Hz |
4k Hz |
8k Hz |
|
LD 4 |
4 |
3 |
11 |
24 |
36 |
49 |
34 |
17 |
LD 5 |
3 |
3 |
9 |
23 |
30 |
40 |
22 |
14 |
LD 6 |
- |
3 |
7 |
20 |
27 |
31 |
16 |
11 |
LD 8 |
2 |
3 |
7 |
16 |
21 |
23 |
9 |
8 |
LD 10 |
3 |
4 |
8 |
20 |
26 |
23 |
10 |
8 |
LD 12 |
1 |
3 |
7 |
16 |
22 |
12 |
6 |
7 |
LD 14 |
- |
3 |
6 |
13 |
18 |
10 |
6 |
7 |
LD 16 |
1 |
3 |
5 |
10 |
13 |
7 |
5 |
6 |
LD 20 |
4 |
8 |
13 |
18 |
24 |
28 |
17 |
16 |
Model | ø Dia.† | Outside ø | l (Length) |
LD 4 |
4 |
8 |
23 5/8 |
LD 5 |
5 |
9 |
23 5/8 |
LD 6 |
6 |
10 1/4 |
23 5/8 |
LD 8 |
8 |
12 1/2 |
23 5/8 |
LD 10 |
10 |
14 |
35 1/2 |
LD 12 |
12 |
17 3/4 |
35 1/2 |
LD 16 |
16 |
25 |
35 1/2 |
Dimensions in inches |
GUIDE SPECIFICATION
Specifier Notes: This guide specification is written in Construction Specifications Institute (CSI) 3-Part Format in accordance with The CSI Construction Specifications Practice Guide, MasterFormat, SectionFormat, and PageFormat.
Specifier Notes: This Section must be carefully reviewed and edited by the Architect or Engineer to meet the requirements of the Project and local building code. Coordinate this Section with Division 01, other specification sections, and the Drawings. Delete all Specifier Notes after editing this Section.
Section numbers and titles are based on MasterFormat 2016 Update.
SECTION 23 33 19
Air Duct Accessories: Duct Silencers
Specifier Notes: This Section covers Fantech’s LD Silencers. Consult Fantech for assistance in editing this Section as required for the Project.
PART 1. GENERAL
1.1 SECTION INCLUDES
A. LD Silencers
1.2 RELATED REQUIREMENTS
Specifier Notes: Edit the following list of related sections as required for the Project. Limit the list to sections with specific information that the reader might expect to find in this Section but is specified elsewhere.
A. Section 22 05 53 – Identification for Plumbing Piping and Equipment
1.3 REFERENCE STANDARDS
Specifier Notes: List reference standards used elsewhere in this Section, complete with designations and titles. Delete reference standards from the following list not used in the edited Section.
A. American Society of Mechanical Engineers (ASME) and American National Standards Institute (ANSI)
a. ASME/ANSI A13.1 – Scheme for the Identification of Piping Systems
B. American Society for Testing and Materials (ASTM)
a. ASTM-A240 – Standard Specification for Chromium and Chromium-Nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels and for General Applications
b. ASTM-A653 – Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed)
c. ASTM-A924 - Standard Specification for General Requirements for Steel Sheet, Metallic-Coated
d. ASTM-E84-9a – Surface Burning Characteristics
e. ASTM-E477-96 – Standard Test Method for Laboratory Measurements of Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers
C. National Fire Protection Agency (NFPA)
a. NFPA 90A – Standard for the Installation of Air-Conditioning and Ventilating Systems
D. Underwriters Laboratories (UL)
a. UL723 – Standard for Test for Surface Burning Characteristics of Building Materials
1.4 PREINSTALLATION MEETINGS
Specifier Notes: Edit the Preinstallation Meetings article as required for the Project. Delete article if not required.
A. Convene preinstallation meeting [1 week] [2 weeks] before start of Work of this Section.
B. Require attendance of parties directly affecting Work of this Section, including Contractor, Architect, installer, and manufacturer’s representative.
C. Review the Following:
a. Materials
b. Installation
c. Adjusting
d. Protection
e. Coordination with other Work
1.5 SUBMITTALS
Specifier Notes: Edit the Submittals article as required for the Project. Delete submittals not required.
A. Comply with Division 01.
B. Product Data: Submit manufacturer’s product data.
C. Shop Drawings: Submit manufacturer’s shop drawings, including plans, elevations, sections, and details.
D. Manufacturer’s Certification: Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application.
E. Warranty Documentation: Submit manufacturer’s standard warranty.
1.6 QUALITY ASSURANCE
A. Manufacturer’s Qualifications:
a. Manufacturer Qualifications: Company specializing in manufacturing products specified in this section with a minimum five years documented experience.
B. Installer's Qualifications:
a. Installer specializing in performing work of this section with minimum two years documented experience with projects of similar scope and complexity.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Delivery Requirements: Deliver materials to site in manufacturer’s original, unopened containers, and packaging, with labels clearly identifying product name and manufacturer.
B. Storage and Handling Requirements:
a. Keep materials in manufacturer’s original, unopened containers, and packaging until installation.
b. Store materials in clean, dry area indoors.
c. Keep materials from freezing.
d. Protect materials during storage, handling, and installation to prevent damage.
1.8 WARRANTY
Warranty Period: 5 Year Warranty
PART 2. PRODUCTS
2.1 MANUFACTURERS
A. Manufacturer: Systemair Mfg. Inc. (dba Fantech), 10048 Industrial Blvd, Lenexa, Kansas 66215, USA
For Canada: Toll Free 800-565-3548, CANADAsupport@fantech.net
For USA: Toll Free 800-747-1762, USsupport@fantech.net
Specifier Notes: Specify if substitutions will be permitted
B. Substitutions: [Not permitted] [Comply with Division 01]
C. Single Source: Provide materials from single manufacturer
2.2 AIR DUCT SILENCERS
A. Air Duct Noise Silencer: LD Silencer Series
a. All silencers shall meet manufacturer’s published performance data.
i. According to ASTM E477
b. Provided the sound attenuation is matched or exceeded, the contractor may convert any or all double wall or sound lined duct work to silencers.
B. Materials
a. Outer Shell: G-90 galvanized steel
i. In accordance with ASTM A-653 and A-924.
ii. By contract, can be specified using stainless steel type 304 or type 316 outer shell.
1. In accordance with ASTM A-240.
iii. Inner Liner: Perforated, with 1/8” perforations on ¼” staggered centers.
1. Overall open area of 23%.
iv. Fiber retention fabric: 0.008” thick, 15.6 lb/ft3 density with an air permeability rate of 9.2 ft3/ft2 · s.
C. Construction
a. Straight Silencers: Inner and outer shells shall be spiral lockseam sheet metal construction.
i. Fiber retention system: Non-woven polyester fabric
ii. Filler Material: Inorganic glass fiber.
1. In accordance with UL 723.
a. Flame Spread: <=25
b. Smoke Developed: <=50
b. Interior Baffle: Aerodynamically efficient
c. 6” Diameter and Larger Straight Silencers: Outer shell corrugated for added strength, rigidity, and to decrease the amount of surface area perpendicular to the noise source.
d. Spiral Seam Slippage: Prevented by flat seam and a mechanically formed indentation along spiral seam
e. Gasket: EPDM rubber gasket.
i. Double-lipped
ii. Conforms to ASTM E84-91a and NFPA 90A
a. Flame Spread: <=25
b. Smoke Developed: <=50
f. No leakage or failure up to differential pressure of 8 in W.G.
D. Performance
a. Acoustic ratings include Dynamic Insertion Loss (DIL) and Self Generated Noise (SN) for both forward and reverse flow conditions
i. In accordance with ASTM Specification E477-96
1. Duct-to-reverberant room test method
ii. Data presented for sizes:
1. 6 in.
2. 12 in.
3. 18 in.
4. 24 in.
5. 30 in.
6. 36 in.
7. 42 in.
b. Static pressure drop not to exceed those listed in specifications or schedule.
E. Certification
a. Conducted by a nationally recognized acoustic test laboratory independent of manufacturer.
F. Models:
a. LD 4
i. Diameter: 4 in.
ii. Outside Diameter: 8 in.
iii. Length: 23 5/8 in.
iv. Metal Gauge: 22-gauge
v. Weight: 11 lbs.
vi. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 4
2. 125 Hz: 3
3. 250 Hz: 11
4. 500 Hz: 24
5. 1k Hz: 36
6. 2k Hz: 49
7. 4k Hz: 34
8. 8k Hz: 17
b. LD 5
i. Diameter: 5 in.
ii. Outside Diameter: 9 in.
iii. Length: 23 5/8 in.
iv. Metal Gauge: 22-gauge
v. Weight: 12 lbs.
vi. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 3
2. 125 Hz: 3
3. 250 Hz: 9
4. 500 Hz: 23
5. 1k Hz: 30
6. 2k Hz: 40
7. 4k Hz: 22
8. 8k Hz: 14
c. LD 6
i. Diameter: 6 in.
ii. Outside Diameter: 10 1/4 in.
iii. Length: 23 5/8 in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 15 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: -
2. 125 Hz: 3
3. 250 Hz: 7
4. 500 Hz: 20
5. 1k Hz: 27
6. 2k Hz: 31
7. 4k Hz: 16
8. 8k Hz: 11
d. LD 8
i. Diameter: 8 in.
ii. Outside Diameter: 12 ½ in.
iii. Length: 23 5/8 in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 18 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 2
2. 125 Hz: 3
3. 250 Hz: 7
4. 500 Hz: 16
5. 1k Hz: 21
6. 2k Hz: 23
7. 4k Hz: 9
8. 8k Hz: 8
e. LD 10
i. Diameter: 10 in.
ii. Outside Diameter: 14 in.
iii. Length: 35 ½ in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 32 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 3
2. 125 Hz: 4
3. 250 Hz: 8
4. 500 Hz: 20
5. 1k Hz: 26
6. 2k Hz: 23
7. 4k Hz: 9
8. 8k Hz: 8
f. LD 12
i. Diameter: 12 in.
ii. Outside Diameter: 17 ¾ in.
iii. Length: 35 ½ in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 44 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 1
2. 125 Hz: 3
3. 250 Hz: 7
4. 500 Hz: 16
5. 1k Hz: 22
6. 2k Hz: 12
7. 4k Hz: 6
8. 8k Hz: 7
g. LD 14
i. Diameter: 14 in.
ii. Outside Diameter: 22 ½ in.
iii. Length: 35 ½ in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 44 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: -
2. 125 Hz: 3
3. 250 Hz: 6
4. 500 Hz: 13
5. 1k Hz: 18
6. 2k Hz: 10
7. 4k Hz: 6
8. 8k Hz: 7
h. LD 16
i. Diameter: 16 in.
ii. Outside Diameter: 25 in.
iii. Length: 35 ½ in.
iv. Corrugated outer shell
v. Metal Gauge: 22-gauge
vi. Weight: 125 lbs.
vii. Noise Suppression dB (mid-frequency Hz):
1. 63 Hz: 1
2. 125 Hz: 3
3. 250 Hz: 5
4. 500 Hz: 10
5. 1k Hz: 13
6. 2k Hz: 7
7. 4k Hz: 5
8. 8k Hz: 6
PART 3. EXECUTION
3.1 EXAMINATION
A. Examine areas to receive LD Silencers.
B. Notify Architect of conditions that would adversely affect installation or subsequent use.
C. Do not begin installation until unacceptable conditions are corrected.
3.2 PREPARATION
A. Prepare surfaces where LD Silencers are to be installed using methods recommended by the manufacturer.
3.3 INSTALLATION
A. Install LD Silencers in accordance with approved submittals and in proper relationship with adjacent construction.
B. For maximum effectiveness, install silence immediately behind a fan or bend.
3.4 PROTECTION
A. Protect LD Silencers from damage during construction.