REBY 75267 UPC#650737449261
Item #: 44926
The SER series lowers demand on air conditionning systems. Air supplied from outdoors enters through the energy recovery core where it transfers the heat and moisture from the incoming air to the outgoing air that was cooled and dried by the building's air conditioner. The air brought into the working area is cooled and the humidity is reduced for maximim comfort. Reduces the load on and air conditioner to save on cooling costs. This unit is designed for warmer, humid climates with longer cooling seasons.
Applications include classrooms, retails shops, hair salons, bars and restaurants, offices, clinic, and animal sheters, etc.
Airflow up to 825 cfm @ 0.4" Ps
Push-pull configuration
External low voltage contacts
Dual service doors & reversible electrical box
External three position switch (Low/Standby/Medium)
Unit | ||
---|---|---|
Frequency | 60 | Hz |
Voltage (nominal) | 120 | V |
Phases | 1~ | |
Input current | 11 | A |
Air flow | 371 | L/s |
Nominal max static pressure (in. w.g.) | 100 | Pa |
Heat Exchanger | ||
---|---|---|
Heat exchanger | Energy recovery |
Others | ||
---|---|---|
Installation type | False ceiling; Horizontal |
Dimensions and weights | ||
---|---|---|
Weight | 209.9 | lb |
|
Supply temperature | Net airflow | Sensible recovery efficiency | Latent recovery efficiency | Total recovery efficiency |
°F (°C) |
cfm (L/s) |
% |
% |
% |
|
Heating |
35 (1.7) |
560 (264) |
67 |
39 |
57 |
35 (1.7) |
420 (198) |
70 |
46 |
62 |
|
Cooling |
95 (35) |
560 (264) |
64 |
28 |
42 |
95 (35) |
420 (198) |
67 |
34 |
47 |
A | B | C | D | E | F | G | I | J | K Drain Spout |
51 2/5 (1306) |
47 1/5 (1199) |
20 (508) |
3 (76) |
8 (203) |
8 (203) |
36 1/4 (921) |
22 (559) |
32 1/2 (826) |
1/2 (13) |
Dimensional information is in inches (mm) |