SHR 8004 HRV

SHR 8004 HRV

Item Number: 40443-1

• Airflow up to 772 cfm @ 0.4" PS
• Push-push configuration
• External low voltage contacts
• Dual service doors & reversible electrical box
• External three position switch (Low/Standby/Medium)
Application

The SHR 8004 Commercial Heat Recovery Ventilation system (HRV) complements today's tight buildings.

How it works

Fantech Heat Recovery Ventilators (HRV) are designed to supply air into a building while exhausting an equal amount of contaminated air to the outside. The aluminum heat exchanger core transfers sensible energy between air streams resulting in tempering of the supply air and reduced loads on the HVAC system.

Defrost cycle

A preset defrost sequence is activated at an outdoor air temperature of 23°F and lower. During the defrost sequence, the supply blower shuts down & the exhaust blower switches to high speed to maximize the effectiveness of the defrost strategy. The unit then returns to normal operation, and continues the cycle.

Technical parameters

Unit
Frequency 60 Hz
Voltage (nominal) 120 V
Phase(s) 1~
Input current 5.3 A
Input power 636 W
Air flow max 364 L/s
Static pressure 100 Pa
Heat exchanger
Exchanger type Heat recovery (aluminium)
Others
Installation placement Horizontal
Dimensions and weights
Weight 194 lb
Certificates
Certificate AHRI, CSA
Supply temperature Net airflow Sensible effectiveness

F° (C°)

cfm (L/s)

%

Heating

35 (2)

800 (378)

56

35 (2)

600 (283)

59

Cooling

95 (35)

800 (378)

46

95 (35)

600 (283)

48

A B C D E F G

36 1/2 (927)

32 3/16 (818)

20 (508)

8 (203)

21 1/2 (546)

35 (889)

25 3/4 (654)

Fans

Two (2) factory balanced fans with backward curved blades. Motors come with permanently lubricated sealed ball bearings and (TOP) thermal overload protected and maintenance-free operation.

Heat recovery core 

Fantech manufactures this fixed plate cross-flow heat exchanger using new 1100 alloy aluminum. Heat exchanger is engineered with a turbulence inducing geometry in order to maximize heat transfer while allowing an effective evacuation of condensate. The plates are hemmed and sealed to ensure no cross-contamination of airstreams. The aluminum core had a plastic handle for easy removal. The unit features two cores, each 12" x 12" (305 mm x 305 mm) with a 15" (380 mm) depth.

Defrost

A preset frost control sequence is initiated if the outdoor temperature falls below the set point of 23°F (-5°C). During the initial stage, the supply blower shuts down & the exhaust blower switches into high speed to eliminate frost build-up in the core. The unit then returns to normal operation for the final stage of the frost control sequence at which time the sequence is repeated if the outdoor air temperatures is still below the set point.

Serviceability 

Cores, filters and drain pan can be accessed easily from both sides of the HRV from hinged access panels. Cores conveniently slide out with only 15" (380 mm) clearance. Blowers can be accessed from both side of the HRV from fastened access panels. Blowers are easily removed by taking off the access panel and sliding the motor plates out of the HRV. A quick connect allows for fast inspection of blowers.

Case

24 gauge galvanized steel. Baked power-coated paint for a superior adhesion and resistance.

Insulation 

Insulated with 1 in. (25 mm) fiberglass with FSK facing and 2 in. (50 mm) of foil-faced high density polystyrene foam on the outdoor air side for condensation control.

Filters

The exhaust and fresh air streams are protected by MERV1 washable filters constructed to meet UL 900. Optional MERV6 filters are direct replacement to the MERV1. Use of MERV6 filters will add an additional system pressure of 0.29in.wg (72 Pa) at 800 cfm (378 l/s).

Controls 

External three (3) position (Reduced/Stand By/Normal) rocker switch that will offer continuous ventilation. Fantech offers a variety of external controls. (see accessories)

Mounting 

Unit may be suspended by using threaded rod, not supplied, or placed on a platform. Unit shall be adaptable for easy service of electrical components. 

Warranty

Limited lifetime on aluminum core, 3 years on motors, and 3 years on parts.

Requirements and standards
• Complies with the UL 1812 requirements regulating the construction and installation of Heat Recovery Ventilators
• Complies with the CSA C22.2 no. 113 Standard applicable to ventilators
• Technical data was obtained from published results of test relating to AHRI 1060 Standards
ECO-TOUCH Pgrm Wall Ctrl - Fantech Item Number: 44929 ECO-TOUCH Pgrm Wall Ctrl

ECO-TOUCH Ctrl Mural Pgrm

.
EDF1 Multi-Func Ctrl - Fantech Item Number: 40375 EDF1 Multi-Func Ctrl

EDF1 Déshum multi-fonctions

.
EDF7 Electronic Dehumidistat - Fantech Item Number: 44883 EDF7 Electronic Dehumidistat

EDF7 Déshum Élec Multi-fonct

.
Filter,MERV13,600-800,Repl.kit - Fantech Item Number: 414936 Filter,MERV13,600-800,Repl.kit

MERV13 Filter kit, LC, 600-800cfm, 4 pcs, 11.5"x15"

.
Filter,MERV8,600-800,Repl.kit - Fantech Item Number: 414933 Filter,MERV8,600-800,Repl.kit

MERV8 Filter kit, LC, 600-800cfm, 4 pcs, 11.5"x15"

.
IR4 Iris Damper - Fantech Item Number: 411234 IR4 Iris Damper

IR4 Registre à Iris

.
IR5 Iris Damper - Fantech Item Number: 411235 IR5 Iris Damper

IR5 Registre à Iris

.
IR6 Iris Damper - Fantech Item Number: 411236 IR6 Iris Damper

IR6 Registre à Iris

.
IR8 Iris Damper - Fantech Item Number: 411237 IR8 Iris Damper

IR8 Registre à Iris

.
MDEH1 Low Voltage Dehumidistat - Fantech Item Number: 40172 MDEH1 Low Voltage Dehumidistat

MDEH1 Déshumidistat

.
MGE4 Metal Exhaust Grill - Fantech Item Number: 411106 MGE4 Metal Exhaust Grill

MGE4 Grille d'évacuation métal

.
MGE5 Metal Exhaust Grill - Fantech Item Number: 411370 MGE5 Metal Exhaust Grill

MGE5 Grille d'évacuation métal

.
MGE6 Metal Exhaust Grill - Fantech Item Number: 411371 MGE6 Metal Exhaust Grill

MGE6 Grille d'évacuation métal

.
MGE8 Metal Exhaust Grill - Fantech Item Number: 411244 MGE8 Metal Exhaust Grill

MGE8 Grille d'évacuation métal

.
MGS4 Metal Supply Grill - Fantech Item Number: 411368 MGS4 Metal Supply Grill

MGS4 Grille d'air frais métal

.
MGS5 Metal Supply Grill - Fantech Item Number: 411369 MGS5 Metal Supply Grill

MGS5 Grille d'air frais métal

.
MGS6 Metal Supply Grill - Fantech Item Number: 411242 MGS6 Metal Supply Grill

MGS4 Grille d'air frais métal

.
MGS8 Metal Supply Grill - Fantech Item Number: 411243 MGS8 Metal Supply Grill

MGS8 Grille d'air frais métal

.
RTS2 Pushbutton Timer - Fantech Item Number: 40164 RTS2 Pushbutton Timer

RTS2 Minuterie à bouton

.
RTS3 Pushbutton Timer - Fantech Item Number: 40376 RTS3 Pushbutton Timer

RTS3 Minuterie à bouton

.