Fantech
ECOM Symbol

SHR 700 Heat Rec Ventilator

Side duct connection HRV, 685 cfm

Item #: 99268

• Airflow up to 723 cfm @ 0.4" PS
• Push-pull configuration
• Removable screw terminal for easy connection
• Dual service doors & reversible electrical box
• External three position switch (Low/Standby/High)
Application
How it works
Defrost cycle

Technical parameters

Unit
Frequency 60 Hz
Voltage (nominal) 120 V
Phases 1~
Input current 5.58 A
MCA 6.88 A
MOP 15 A
Input power 670 W
Air flow max 341 L/s
Nominal max static pressure 100 Pa
Others
Installation type Horizontal
Dimensions and weights
Weight 215 lb
Certificates
Certificate CSA, AHRI 1060 Components
Images Wiring - SHR 700 Heat Rec Ventilator - Fantech
 

Supply Temperature

Net Airflow

Sensible net effectiveness

Total net effectiveness

 

°F (°C)

cfm (L/s)

%

%

Heating

35 (1.7)

690 (326)

55

36

 

35 (1.7)

518 (244)

56

37

Cooling

95 (35)

690 (326)

55

21

 

95 (35)

518 (244)

56

21

Images Dimensions - SHR 700 Heat Rec Ventilator - Fantech
A B C D E F G I J K (Drain)

36 1/2 (927)

32 3/16 (818)

13 7/8 (352)

2 3/8 (60)

8 (203)

8 (203)

36 1/4 (921)

22 (559)

32 1/2 (826)

1/2 (13)

Dimensional information is in inches (mm).

GUIDE SPECIFICATION 

Specifier Notes: This guide specification is written in Construction Specifications Institute (CSI) 3-Part Format in accordance with The CSI Construction Specifications Practice Guide, MasterFormat, SectionFormat, and PageFormat.  

Specifier Notes: This Section must be carefully reviewed and edited by the Architect or Engineer to meet the requirements of the Project and local building code.  Coordinate this Section with Division 01, other specification sections, and the Drawings.  Delete all Specifier Notes after editing this Section. 

Section numbers and titles are based on MasterFormat 2016 Update. 

SECTION 23 72 15 

HEAT RECOVERY VENTILATOR 

Specifier Notes:  This Section covers Fantech’s SHR Series of Heat Recovery Ventilators. Consult Fantech for assistance in editing this Section as required for the Project.   

PART 1. GENERAL 

1.1    SECTION INCLUDES 

        A.  Heat Recovery Ventilators 

1.2    RELATED REQUIREMENTS 

Specifier Notes:  Edit the following list of related sections as required for the Project. Limit the list to sections with specific information that the reader might expect to find in this Section, but is specified elsewhere. 

        A.Section 23 08 00 – Commissioning of HVAC 

1.3    REFERENCE STANDARDS 

Specifier Notes:  List reference standards used elsewhere in this Section, complete with designations and titles.  Delete reference standards from the following list not used in the edited Section. 

    A.    ANSI/AHRI 1060 Components– Performance Rating of Air-to-Air Heat Exchangers for Energy Recovery Ventilation Components. 

    B.    ANSI/AMCA 300 – Reverberant Room Method for Sound Testing of Fans. 

    C.    ASHRAE 84 – Method of Testing Air-to-Air Heat Exchangers. 

    D.    ASTM A 792/A 792M – Standard Specification for Steel Sheet, 55 % Aluminum-Zinc Alloy-Coated by the Hot-Dip Process. 

    E.    CSA C22.2, No. 77 – Motors with Inherent Overheating Protection. 

    F.    CSA C22.2, No. 100 – Motors and Generators. 

    G.    CSA C22.2, No. 113 – Fans and Ventilators. 

    H.    CSA C22.2, No. 236 – Heating and Cooling Equipment. 

    I.    ISO 9001:2015 – Quality Management Systems – Requirements. 

    J.    NFPA 70 – National Electrical Code (NEC). 

    K.    UL 723 – Standard for Test for Surface Burning Characteristics of Building Materials. 

    L.    UL 900 – Standard for Air Filter Units. 

    M.    UL 1004-2 – Standard for Impedance Protected Motors. 

    N.    UL 1004-3 – Standard for Thermally Protected Motors. 

    O.    UL 1004-7 – Standard for Electronically Protected Motors. 

    P.    UL 1812 – Standard for Ducted Heat Recovery Ventilators. 

    Q.    UL 2111 – Standard for Overheating Protection for Motors. 

1.4    PREINSTALLATION MEETINGS 

Specifier Notes:  Edit the Preinstallation Meetings article as required for the Project. Delete article if not required. 

        A.    Convene preinstallation meeting [1 week] [2 weeks] before start of Work of this Section. 

        B.    Require attendance of parties directly affecting Work of this Section, including Contractor, Architect, installer, and manufacturer’s representative. 

        C.    Review the Following: 

                1.Materials 

                2.Installation 

                3.Adjusting 

                4.Protection 

                5.Coordination with other Work 

1.5 SUBMITTALS 

Specifier Notes:  Edit the Submittals article as required for the Project. Delete submittals not required. 

        A.    Comply with Division 01. 

        B.    Product Data:  Submit manufacturer’s product data, including installation instructions. 

        C.    Shop Drawings:  Submit manufacturer’s shop drawings, including plans, elevations, sections, and details.   

                1.    Wiring Diagrams:  Indicate wiring for each item of equipment and interconnections between items of equipment. 

                2.    Include manufacturer’s names, model numbers, ratings, power requirements, equipment layout, device arrangement, complete wiring point-to-point diagrams, and conduit layouts. 

        D.    Manufacturer’s Certification:  Submit manufacturer’s certification that materials comply with specified requirements and are suitable for intended application. 

        E.    Operation and Maintenance Data: 

                1.Submit manufacturer’s operation and maintenance manual; including the following: 

                    a.    Operation, maintenance, adjustment, and cleaning instructions. 

                    b.    Troubleshooting guide 

                    c.    Parts list 

                    d.    Electrical wiring diagrams if required. 

                2.    Provide detailed information required for Owner to properly operate and maintain equipment. 

        F.    Warranty Documentation:  Submit manufacturer’s standard warranty. 

1.6 QUALITY ASSURANCE 

       A. Manufacturer’s Qualifications:   

            1. Manufacturer regularly engaged in the manufacturing of air handling units, heat or energy recovery ventilators in the last 10 years. 

            2. ISO 9001 Certified  

        B. Installer's Qualifications: 

             1. Installer regularly engaged in installation of air handling units, heat or energy recovery ventilators to that specified for a minimum of 5 years. 

                2. Use persons trained for installation of air handling units, hear or energy recovery ventilators 

1.7 DELIVERY, STORAGE, AND HANDLING 

      A. Delivery Requirements:  Deliver materials to site in manufacturer’s original, unopened containers and packaging, with labels clearly identifying product name and manufacturer. 

      B. Storage and Handling Requirements: 

                1. Store and handle materials in accordance with manufacturer’s instructions. 

                  2. Keep materials in manufacturer’s original, unopened containers and packaging until installation. 

                    3. Store materials in clean, dry area indoors. 

                    4. Keep materials from freezing. 

                    5. Protect materials during storage, handling, and installation to prevent damage. 

1.8 WARRANTY 

Warranty Period:  3 years 

PART 2. PRODUCTS 

2.1 MANUFACTURERS 

        A. Manufacturer:  Fantech Inc., 50 Kanalflakt Way, Bouctouche, New Brunswick E4S 3M5, Canada. For Canada:  Toll Free 800-565-3548, CANADAsupport@fantech.net  

For USA: Toll Free 800-747-1762, USsupport@fantech.net 

 Specifier Notes:  Specify if substitutions will be permitted. 

        B.Substitutions: [Not permitted] [Comply with Division 01]. 

        C.Single Source:  Provide materials from single manufacturer. 

2.2 HEAT RECOVERY VENTILATORS 

        A. Heat Recovery Ventilators: SHR Series 

        1.    Models:  SHR450, SHR700, SHR800, SHR1200, SHR1400 

        2.    Indoor, compact, light-commercial heat recovery ventilators. 

Specifier Notes:  Specify required model. Consult Fantech for assistance in determining heat recovery ventilator model for the specific application. 

        B.    General 

            1.    Each Unit or Group of Units:  Capable of operating in any mode independently or dependently of other systems. 

            2.    Capable of changing modes with no interruption to system operation. 

            3.    Listed under CSA C22.2, No. 113-15/UL 1812. 

            4.    Wiring:  NFPA 70. 

            5.    Performance:  As scheduled on the Drawings. 

            6.    Equip with control systems. 

            7.    Perform all functions necessary for operation. 

            8.    Ventilation to Building:  Not to cease in any mode based solely on operational temperature of minus 13 to 104 degrees F (minus 25 to 40 degrees C). 

            9.    Capable of changing modes with no interruption to system operation. 

            10.    Capable of transferring both sensible and latent heat between the fresh and stale air streams.  

            11.    Capable of operating in winter and summer conditions without imbalance or loss of ventilation capacity greater than specified in design. 

        C.    Unit Cabinet 

                12.    Single Wall Cabinet:  

                        a.    22-gauge sheet galvanized steel, G90 coated with lapped corners. 

                        b.    Seams:  Sealed, requiring no caulking in field. 

                13.    Insulation within a Single Wall:  

                        a.    1.0-inch (25.4-mm) fiberglass. 

                        b.    Flame Spread Index, UL 723:  Not over 25. 

                        c.    Smoke Developed Index, UL 723:  Not over 50. 

                14. Cabinet Doors & Panels 

                        a.    22-gauge G90 pre-painted sheet galvanized steel. 

                        b.    1.0-inch (25.4-mm) fiberglass. 

        D.    Fans 

                1.    Direct-drive, backward-inclined, motorized ECM impellers 

                2.    Fan Motors: 

                        a.    Maintenance-free, permanently lubricated, sealed ball bearings. 

                        b.    Thermal overload protected (TOP). 

                        c.    UL listed to UL1004 and/or UL2111, CSA C22.2 No. 77 and No.100 

                        d.    IP Protection:  Class 44. 

                3.    Separate fans for exhaust and supply blowers. 

        E.    Heat recovery exchanger 

                1.    Exchanger Construction:  Fixed plate cross-flow heat exchanger using 1100 alloy aluminum and capable of transferring sensible heat between air streams. The heat recovery exchanger shall be engineered with a turbulence inducing geometry to maximize heat transfer while allowing an effective evacuation of condensate. The plates shall be hemmed to avoid cross-contamination of airstreams. The flame spread index of the heat recovery core shall not be over 25 and its smoke development index shall not be over 50 when tested in accordance with the Standard for Tests for Surface Burning Characteristics of Building Material, UL723. 

                2.    Cross-flow construction type. 

                3.    Free cooling capacity. 

                4.    Performance:  Certified and listed by AHRI Components. 

                5.    Frame Material:  Corner profiles in PVC and gables in aluminum-zinc sheet steel 

                6.    Effectiveness of exchanger:  Documented in accordance with ASHRAE 84 and AHRI 1060 Components. 

                7.    Flame Spread Index, Heat Recovery Exchanger, UL 723:  Not over 25. 

                8.    Smoke Developed Index, Heat Recovery Exchanger, UL 723:  Not over 50. 

        F.    Air filters 

                1.    Supply and exhaust air protected by MERV3 mesh filters constructed to meet UL 900. (Optional MERV8 or MERV13 filters are direct replacement to the MERV3 in size) 

        G.    Frost control 

                1.    Frost control sequence (pre-set) initiated if the outdoor air temperature falls below the set point of 23°F (-5°C) 

        H.    Electrical 1 Phase Input Voltage  

                1.    Electrical Power:  120 VAC, 1 Phase, 60 Hz, MOP 15A 

                2.    Internal Electrical Components:   

                    a.    Factory wired for single-point power connection. 

                    b.    UL Listed or Recognized and CSA Certified or Accepted where applicable and wired in compliance with the National Electrical Code. 

                3.    Electrical Box Components:  Accessible without stopping unit or opening doors. 

                4.    Electrical Box: 

                        a.    Isolated from airflow paths.

                        b.    Protect integral wires and connections. 

        I.    Serviceability 

                1.    Access Panel:  Hinged and/or screwed access panel on front of unit.

                2.    Heat Recovery Exchangers, Filters, and Motors:  Serviceable from front of unit. 

                3.    Fan Assemblies:  Mounted on removable base.

                4.    Heat Recovery Exchangers and Filters:  Mounted on slide-out rails. 

2.3 ACCESSORIES 

        A.    Shutter damper with spring-return actuators for Rectangular Ducts 

        Specifier Notes:  Delete accessories not required. 

                1.    Model: [“EFD 14-8”] [“EFD 20-8”] [“EFD 24-8”]  

                2.    Spring-return actuators: motorized, 24 V motors with spring-return actuators. 

                3.    Leakage: less than 1% 

2.4 ASSEMBLY 

        A.    Factory assembled and wired heat recovery ventilators 

2.5 SOURSE QUALITY CONTROL 

        A.    Run test at factory  

PART 3. EXECUTION 

3.1 EXAMINATION 

        A. Examine areas to receive heat recovery ventilators. 

        B. Notify Architect of conditions that would adversely affect installation or subsequent use. 

        C. Do not begin installation until unacceptable conditions are corrected. 

3.2 PREPARATION 

        A. Prepare surfaces where heat recovery ventilators are to be mounted. 

        B. Ensure surfaces are flat, level, plumb, and can support weight of heat recovery ventilators 

3.3 INSTALLATION 

        A.    Install heat recovery ventilators in accordance with manufacturer’s instructions at locations indicated on the Drawings  

    B.    Install heat recovery ventilators in accordance with NFPA 70 

    C.    Install heat recovery ventilators, rod mount or seat on a platform, level, plumb, and secure.  

    D.    Do not expose electronic components to temperatures below 32 degrees F (0 degrees C) or above 122 degrees F (50 degrees C).  

3.4 ADJUSTING 

        A. Adjust heat recovery ventilators for proper operation in accordance with manufacturer’s instructions. 

3.5 DEMONSTRATION 

        A.    Demonstration  

                1.       Demonstrate that heat recovery ventilators function properly in every respect 

                2.       Provide hands-on demonstrations of operation of system components and complete system, including user-level program changes and function 

                3.       Provide instruction and training by factory-trained and certified representative of manufacturer 

3.6 PROTECTION 

        A. Protect installed heat recovery ventilators from damage during construction. 

END OF SECTION

CO2RT-R Control - Fantech
Item #: 99315
CO2RT-R Control

0-2000 ppm w/o display, surface mount

.
ECO-Feel® Auto IAQ control - Fantech
Item #: 414729
ECO-Feel® Auto IAQ control

TVOC sensing controller, ECO-mode, w/o display, 4 wires

.
ECO-Touch® Auto IAQ control - Fantech
Item #: 414727
ECO-Touch® Auto IAQ control

TVOC sensing controller, multi-function, touchscreen,4 wires

.
ECO-Touch® control - Fantech
Item #: 414728
ECO-Touch® control

Multi-function programmable controller, touchscreen,4 wires

.
BPM 08-14 Bypass module - Fantech
Item #: 99300
BPM 08-14 Bypass module

3-way bypass module for recirculation, 8"x14" duct

.
EFD 14-8 - Fantech
Item #: 99303
EFD 14-8

14"x8" Shutter damper with spring-return actuators, 24V

.
EDF1 Electronic control - Fantech
Item #: 40375
EDF1 Electronic control

Low / Intermittent / High, 1-gang box mount, 2 wires

.
EDF7 Electronic control - Fantech
Item #: 44883
EDF7 Electronic control

w/dehumidification function, display, surface mount, 2 wires

.
Filter,MERV13,600-800,Repl.kit - Fantech
Item #: 414936
Filter,MERV13,600-800,Repl.kit

MERV13 Filter kit, LC, 600-800cfm, 4 pcs, 11.5"x15"

.
Filter,MERV8,600-800,Repl.kit - Fantech
Item #: 414933
Filter,MERV8,600-800,Repl.kit

MERV8 Filter kit, LC, 600-800cfm, 4 pcs, 11.5"x15"

.
IR4 Iris Damper - Fantech
Item #: 411234
IR4 Iris Damper

4" iris damper w/manual adjuster

.
IR5 Iris Damper - Fantech
Item #: 411235
IR5 Iris Damper

5" iris damper w/manual adjuster

.
IR6 Iris Damper - Fantech
Item #: 411236
IR6 Iris Damper

6" iris damper w/manual adjuster

.
IR8 Iris Damper - Fantech
Item #: 411237
IR8 Iris Damper

8" iris damper w/manual adjuster

.
MDEH 1 Dehumidistat - Fantech
Item #: 40172
MDEH 1 Dehumidistat

low voltage, 20-80% RH, surface mount, 2 wires

.
MGE4 Metal Exhaust Grill - Fantech
Item #: 411106
MGE4 Metal Exhaust Grill

4" duct metal grille w/collar, exhaust

.
MGE5 Metal Exhaust Grill - Fantech
Item #: 411370
MGE5 Metal Exhaust Grill

5" duct metal grille w/collar, exhaust

.
MGE6 Metal Exhaust Grill - Fantech
Item #: 411371
MGE6 Metal Exhaust Grill

6" duct metal grille w/collar, exhaust

.
MGE8 Metal Exhaust Grill - Fantech
Item #: 411244
MGE8 Metal Exhaust Grill

8" duct metal grille w/collar, exhaust

.
MGS5 Metal Supply Grill - Fantech
Item #: 411369
MGS5 Metal Supply Grill

5" duct metal grille w/collar, supply

.
MGS6 Metal Supply Grill - Fantech
Item #: 411242
MGS6 Metal Supply Grill

6" duct metal grille w/collar, supply

.
MGS8 Metal Supply Grill - Fantech
Item #: 411243
MGS8 Metal Supply Grill

8" duct metal grille w/collar, supply

.
RTS2 Push-button timer - Fantech
Item #: 40164
RTS2 Push-button timer

20 min push-button timer, 1-gang box mount, 2 wires

.
RTS5 Push-button timer - Fantech
Item #: 44794
RTS5 Push-button timer

20/40/60 min push-button timer, 1-gang box mount, 2 wires

.